Camco RV Power Defender Voltage Protector - 50 Amp Showing Open Neutral When Plugged Into Generator
Updated 04/05/2021 | Published 04/01/2021 >
Question:
My Camco analyzer is showing an open neutral when plugged into generator, but was working fine a few hours ago. How can I fix this?
asked by: Elizabeth B
0
Expert Reply:
If you are connecting the Camco RV Power Defender Voltage Protector - 50 Amp, # CAM55306, directly to the generator and getting an "Open Neutral" fault when then connecting to RV you most likely have an issue either with the generator outlet the cord running to your RV. I recommend inspecting the outlet, and the RV's power cord for damage, wear or loose connections.
expert reply by:
Michael R
0
Product Page this Question was Asked From
Camco RV Power Defender Voltage Protector - 50 Amp
- RV Surge Protector
- Surge Protector
- 50 Amp
- Portable
- Camco
more information >
Continue Researching
- Q&A: High Low Adapter For Dirt Bike Carrier
- Q&A: Looking For High-Low Adapter For 2-1/2" Hitch With 12" Drop
- Q&A: Why Does the Lube Plate Fall Off My Trailer
- Q&A: Is Lube Plate Needed When Using Pivoting Pin Box Like MorRyde Orbital Pin Box
- Q&A: Correct Gen-Y Gooseneck Pin Box for a Brinkley 5th Wheel Trailer
- Article: 30-Amp and 50-Amp RV Service: What's the Difference?
- Q&A: Replacement Follow Leg for a 2006 Alpenlite 31CK 5th Wheel
- Q&A: Troubleshooting 5th Wheel Landing Gear That Retracts But Wont Extend
- Article: Fifth Wheel Trailer Hitch Information and Installation Tips
- Article: Trailer Wiring Diagrams
- Article: Brake Controller 7- and 4-Way Installation Kit (ETBC7)
- Article: 4 Steps to Choosing Your 5th Wheel Pin Box
- Article: RV Electrical Power Systems
- Article: What are the Common Types of Propane Fittings Used on RVs?