Troubleshooting An A-iPower Generator That Starts But Dies When Switched To Run Position
Updated 05/28/2024 | Published 09/10/2023 >
Question:
Hello, I have a I power generator. SC 2000i turns on fine but when I turn it to rum it turns off
asked by: Maria E
0
Expert Reply:
Typically if your A-iPower 2,000-Watt Portable Inverter Generator # 289-SUA2000i will start but dies after switching over to run you're dealing with a fuel issue. This could be a lack of fuel, bad fuel, or debris clogging up the fuel line. Your carburetor could also be clogged, which is very common if the generator sat for awhile with fuel in it. I recommend siphoning out the fuel you have in it and cleaning out the carburetor and then refilling with fresh fuel.
expert reply by:
Kevin C
0

Continue Researching
- Q&A: Troubleshooting An A-iPower Generator That Won't Stay Running When Switched To The Run Position
- Q&A: Troubleshooting An A-iPower Inverter Generator That Won't Start
- Shop: Thule HideAway Awning for ProMaster or Sprinter - Roof Mount - 8' Long x 10' 8" Wide
- Shop: Lippert Standard Baggage Door Latch Kit - Black
- Q&A: Troubleshooting An A-iPower Generator That Runs For 20 Seconds And Shuts Off
- Shop: Solera RV Slide-Out Awning - 133" Wide - Black
- Shop: Solera RV Slide-Out Awning - 198" Wide - Black
Brian B.
5/28/2024
Mine is brand new out of the box, fuel is good as my mower runs fine off the fuel. What else could it be? Is there something I need to remove ? I.e. some type of packing or safety feature?