Should Propane Regulator Changeover Lose Pressure When Switching Tanks  

Updated 06/11/2019 | Published 06/10/2019

Question:

i have a 2014 rockwood 33 ft when my propane changeover switches over there is not enough pressure to have the stove and the furnace going i changed out the high pressure regulator and the hose on that side too no difference wondering if it could be the changeover regulator

1

Helpful Expert Reply:

It does sound like an issue with your changeover because when using a regulator such as the Camco Automatic Changeover 2-Stage Propane Regulator for Dual Propane Tanks # CAM59005, the auxiliary tank will take over and start supplying propane once the primary tank is empty enough that the pressure falls to less than the auxiliary tank, which means your pressure should not be less when switching tanks, and if this isn't happening the changeover regulator could be faulty.

expert reply by:
1
Kyle S